10KVA - 80KVA Three se On Frequency Smart Power UPSHigh Frequency OnQueen Star Plus Strar Series 33Q10K-80K(3in/3out)Features: 1: The load PFC is 0.82: Environment Friendly3: Support the generator4: Sufficient Expansion Slots5: Output transfer time is 0ms6: Adaptive Load Management7: Programmable power management outlets 8: Wide range of input voltage and frequency9: DSP technology guarantees high performance 10: Standard communication options: RS-232 communication port11: Sixth generation IGBT,much higher efficiency, lowetemperaturer,more reliable12: Independent ventilation enhance durable operation under harsh environment13: Exnt input frequency range makes UPS suitable to different power supply devices, i.e. generator set
Technical Specification:
Index
33Q 10KL
33Q 20KL
33Q 30KL
33Q 40KL
33Q 60KL
33Q 80KL
Comments
Input
Input voltage
Rated voltage
380VAC/220VAC
380VAC
se
three se with ground
Turn on voltage range
(120±5~274±5)VAC
(207±9~475±9)VAC
Bypass voltage range
(60±5~300±5)VAC
(105±9~518±9)VAC
Could be adjusted by software.
Bypass low loss
60VAC~220VAC(default 60VAC)
105VAC~380VAC(default 105VAC)
Bypass low comeback
Low loss +5VAC
Low loss +17VAC
Bypass high loss
220VAC~300VAC(default 300VAC)
380VAC~475VAC(default 475VAC)
Bypass high comeback
High loss -5VAC
High loss -17VAC
losscomeback
(120±5) VAC /(140±5) VAC
(207±9) VAC (242±9) VAC
loadâ¤50%
(140±5) VAC /(160±5) VAC
(242±9) VAC(276±9) VAC
50%â¤90%
(160±5) VAC /(175±5) VAC
(276±9) VAC(302±9) VAC
load>90%
losscomeback
(275±5)VAC/(260±5)VAC
(475±9)VAC(449±9)VAC
Input frequency
Rated frequency
50Hz
Frequency low loss
(40~49) ±0.2Hz(default:46Hz)
Could be adjusted by software.
Frequency low comeback
Frequency low loss +0.5Hz
Frequency high loss
(51~60)±0.2Hz(default:54Hz)
Frequency high comeback
Frequency high loss -0.5Hz
Input power factor
Could be adjusted by software.
> 0.99
33Q 10-40KL:220VAC,full R load33Q 60-80KL: 380VAC,full R load
Generator
Support generator input
Generator ratingâ¥2*UPS rating
Input current
Rated current
14A
28A
42A
67A
80A
105A
Input THDI
<= 10%
Output protection
Rating protection
32A Breaker
50A Breaker
60A Breaker
80A Breaker
100A Breaker
125A Breaker
Output power
VA/watt
10KVA/8KW
20KVA/16KW
30KVA/24KW
40KVA/32KW
60KVA/48KW
80KVA/64KW
Rated voltage
220VAC
380VAC
Sine wave
Voltage range
200/208/220/230/240VAC
345/359/380/397/415 VAC
33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC/200VAC.33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC/359VAC.
Voltage regulation
±1%
Voltage distortion
â¤5%
â¤10%
Full RCD load
â¤3%
Full R load
DC offset
â¤200mV
Transient response
â¤9%
R load 0%~100%~0%
â¤6%
R load 20%~100%~20%
Transient recovery
â¤60ms voltage recovery to 90%
Full RCD load
Bypass output before turn-on
YES
Crest ration
3:1
Output frequency range
Normal mode
1,Same as input frequency(46Hz~54Hz)2,50Hz(Input frequency>54Hz or Input frequency<46Hz)