Quick Details
- Color:Red
- Processing Time:15-25days
- Port:Shenzhen
- Supply Ability: -
- Brand Name:sumring
- Model Number:SR-P01-16
- Place of Origin:Guangdong
- Brand Name:Sumring
Fire alarm control panel
SR-P01-16 16 zones conventional fire alarm control panel
The SR-P01 Series Conventional Fire Alarm Control Panel is a 24 volt, four to
sixteen-zone, Class B, Conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly cost-effective SR-P01 Series can be used
in a variety of low- to mid-sized applications.
Main features:
Four, Eight, Sixteen Zone Style B (Class B) Initiating Device Circuits (IDCs), All
zones accept
two-wire smoke detectors and any normally-open contact
devices.
Two Supervisory Input with DC12V output, ideal to connect security alarm
devices.
Three General Alarm, Trouble and Supervisory, Form A Relay
Output.
One, Two, Four Built-in Sound Output, Style Y (Class B) Notification Appliance (Signal)
Circuits
(NACs), NACs may be programmed: Silenceable or
Non-Silenceable.
3.0 amps of total system power. Resettable DC24V & Non-resettable DC24V
Output.
Zone Input Short Circuit can be set to “Alarm” or “ Fault”
mode.
RS485 Communication Port (optional).
Automatic/Manual mode can be programmed.
Disable/Enable control per Zone (IDC) can be programmed.
Disable/Enable Sound Output(NACs) can be programmed.
Main features:
AC POWER: 220VAC, 50 Hz.
BATTERY: Sealed lead-acid batteries only. Maximum charging circuit: 27.6VDC @ 0.8 amp
for
normal flat charge. Maximum battery charger capacity: 18AH
battery.
NOTE: Two 10AH batteries can be housed in the cabinet. Larger batteries require a
separate
battery box.
Total DC24V system power: 3.0 amps.
Maximum current per NAC: 1.25 amps.
Maximum battery charging capability: 18 AH.
Resettable four-wire smoke detector power output.
Non-resettable power output.
Integral Form-A Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @ 30
VDC
(resistive), 2.0 amps @ 30 VAC (resistive)