Quick Details
- Processing Time:-
- Port:-
- Supply Ability: -
- Brand Name:PEPPERL+FUCHS
Emergency stop mushroom button 39 mm, red, key release - 1x NO / 1x NC
Ex de and Ex tb certified
Full equipment certified
Polyamide housing for panel mount
Installation in Zone 1, Zone 2, Zone 21 and Zone 22
Cable Gland M20 integrated in protective cover
Degree of protection IP66
Electrical specifications
Operating voltage
250 V max.
Operating current
16 A max.
Terminal capacity
2.5 mm2
Terminal torque
0.8 Nm
Function
mushroom button
Color
red
Contact configuration
1x NO / 1x NC
Switching diagram
PD-C147617A PD-C147538A see switching diagram overview
Usage category
AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A
Number of poles
2
Operator action
latching , key release
Lockable
yes
Mechanical specifications
Cable type
non-armored cables
Clamping range (D)
5.5 ... 13 mm (D)
Covering
Protective cover fully detachable
Cover fixing
Phillips head screw
Degree of protection
IP66
Cable entry
Number of cable entries
1x M20 cable gland in protective cover
Material
Housing
Polyamide (PA)
Finish
inherent color black
Seal
silicone
Washer gasket
silicone
Mass
150 g max.
Dimensions
Height (A)
77 mm (A)
Width (B)
44 mm (B)
Depth (C)
105 mm (C)
Actuator head diameter (D2)
39 mm (D2)
Panel wall thickness (PT)
1 ... 6 mm (PT)
Diameter thru-hole (DT)
30.6 mm (DT)
Length outside enclosure (H)
41.6 mm (H)
Width across flats (SW1)
24 mm (SW1)
Total length (L)
154.1 mm (L)
Tightening torque
Nut torque at enclosure (SW1)
2 Nm (SW1)
Mounting
via actuator head
Ambient conditions
Ambient temperature
-40 ... 50 °C (-40 ... 122 °F)
Data for application in connection with hazardous areas
EU-type examination certificate
CML 16 ATEX 3106X
Marking
II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db
International approvals
IECEx approval
IECEx CML 16.0046X
Conformity
Degree of protection
EN 60529
Usage category
IEC / EN 60947
CE marking
0080 or 0102, see type label
General information
Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see .